DRY HYDRANT MANUAL 
                              
                              
                              
                              
        A Guide for Developing Alternative 
      Water Sources for Rural Fire Protection 
From code originally developed for Summit County, Colorado
                      ALTERNATE WATER SUPPLY POLICY 
 
SCOPE: 
 
This policy is intended to offer guidance and assistance to the property owner, 
contractor and developer in meeting the requirements of the Uniform Fire Code 
and Chapter 14 (as amended) of the Uniform Building Code for the provision of 
adequate water supplies for rural firefighting. This policy does not necessarily 
meet ISO requirements for installation of a draft fire hydrant. 
 
GOALS: 
 
   1.      To reduce ISO ratings 
   2.      To design each installation with the capability of flowing 1,000 gpm 
   3.      To obtain points for fire mitigation 
   4.      To function to protect life and property 
 
DEFINITION: 
 
A draft fire hydrant is a specially designed and constructed fire hydrant, which 
has been approved by the Fire Department having jurisdiction. This draft fire 
hydrant shall be connected to a year-round draft water source of sufficient 
capacity to meet the fire fighting needs of the property(s) involved. Fire hydrants 
which are connected to a pressurized municipal watercourse are not covered by 
this policy. 
 
 
                                       PERMITS 
 
   A.      A review of the draft fire hydrant plans shall be completed by the Fire 
           Department having jurisdiction prior to issuing a grading permit to allow 
           construction of a draft hydrant. A site plan review shall be used to 
           determine site-specific requirements including, but not limited to depth 
           of pipe, required insulation materials, backfill requirements, and draft 
           site requirement. Additionally, information containing drought 
           conditions for the past 50 years may be required to be submitted. 
   B.      A statement signed by the owner of the property on which the draft 
           hydrant will be located, shall authorize access to and use of the draft 
           fire hydrant by the Fire Department and its agents. The Fire 
           Department having jurisdiction will be using water under the 
           presumption of non-injury/non-consumption for fire emergency use. 
 
                                                                                    2
                            ACCEPTANCE TESTING 
                                            
   A.    All draft hydrants shall be subject to acceptance testing approved by 
         the Fire Department having jurisdiction prior to being accepted as a 
         water source. Acceptance testing shall include GPM verification of the 
         water source. Maintenance and testing will return water within 200 feet 
         of its drainage. 
                                            
                                 MAINTENANCE 
 
   A.    Draft fire hydrants require bi-annual testing and maintenance.  The 
         hydrants should be tested with a pumper. Back flushing followed by a 
         pumper test at a maximum designed flow rate, with records kept of 
         each test, is required. Tests of this kind will not only verify proper 
         condition, but also keep the line and strainer clear of silt and the water 
         supply available for any fire emergency. 
   B.    Any homeowner using the draft hydrant who has obtained points for 
         mitigation or an ISO classification shall be responsible at all times for 
         keeping the draft hydrant and its protective barriers free from 
         obstruction by vehicles, materials, structures, snow, or other 
         obstructions, and shall maintain the draft hydrant in a serviceable 
         condition at all times. 
   C.    It shall be the responsibility of the property owners using the hydrant 
         for mitigation of ISO classification purposes to immediately notify the 
         Fire Department having jurisdiction of any draft hydrant which is 
         obstructed, damaged, or our of service for any reason. 
 
                                            
                            DESIGN REQUIREMENTS 
 
   A.    All draft hydrants shall be located within eight (8) feet of a road 
         maintained year-round. Access to the system shall conform to the road 
         and bridge standards in Appendix D "Access and Water Supply". 
   B.    All draft hydrants shall have a single draft connection located a 
         maximum of 30” measured from the grade level of the roadway where 
         the fire apparatus will be parked to the top of the draft hydrant’s 
         threaded connection. Additionally, life shall be determined by 
         measuring from year-round low level of the water surface to the truck 
         intake. 
   C.    All draft hydrants shall have a draft tube running horizontally from the 
         water source to the base of the riser consisting of a minimum of six (6) 
         inch PVC. PVC pipe meeting AWWA specification C9000 with a SDR 
                                                                                    3
          of 18 or less may be required through or under foundations and under 
          driveways (Schedule 80 pipe or its equivalent may be deemed 
          necessary in some instances). All joints must be sealed watertight, 
          airtight and rootproof. 
   D.     The piping shall be placed in bedding material of ¾” washed or screen 
          rock or in native soils, providing that the native soils contain no sharp 
          materials or stone larger than two and one-half (2.5) inches that may 
          damage the piping. 
   E.     The bedding material shall be placed to a depth of four (4) inches 
          below the pipe and six (6) inches above the top of the pipe. 
   F.     The draft fire hydrant pipe extending from the water source to the rise 
          pipe connection shall have a grade of minimum .5% to a maximum 2% 
          toward the water source. (This excludes the riser section immediately 
          preceding the fire department connection). 
   G.     All draft fire hydrants shall have a single draft connection consisting of 
          an approved fitting and cap having a 6” male NST threads.  (Size of 
          connection shall be determined by the Fire Department having 
          jurisdiction.) 
   H.     No more than two elbows are recommended.  Elbows may be 90 or 45 
          degree bends (See Figure 1). 
 
                                            
                         INSTALLATION REQUIREMENTS 
 
   A.     All draft fire hydrants shall be painted red in color (oil base paint) with 
          reflective tape, to protect PVC pipe from the adverse effects of sunlight 
          and to assist in the rapid location and identification by the Fire 
          Department. 
   B.     All draft fire hydrants shall be protected from damage by snowplows, 
          motor vehicles, etc., by the installation of three (3) steel pipes buried 
          three (3) feet into the ground with four (4) feet extending above the 
          grade level of the roadway. The entire pipe shall be filled with concrete. 
          The protective pipes shall be located in a triangle configuration 
          approximately three (3) feet away from the draft hydrant. Steel pipes 
          shall be painted with red oil base paint and reflective tape. 
   C.     All draft hydrants shall be required to have a sign stating "draft hydrant” 
          in a location acceptable to the Fire Department having jurisdiction. 
 
The above policy is subject to change or modification by the Fire Department 
having jurisdiction. 
                                                                                      4
 
                                           
                        MAXIMUM LIFT CONSIDERATIONS 
 
Definition:  Lift shall be determined by measuring from the lowest level of the 
water surface to the truck intake, which is 36” above grade. 
 
 
 
Maximum vertical lift recommendations: 
 
                  Elevation                               Do Not Exceed   
                 4,000 ft                                    13 ft 
                 5,000 ft.                                   12 ft. 
                 6,000 ft.                                   11 ft. 
                 7,000 ft.                                   10 ft. 
                 8,000 ft.                                   9 ft. 
                 9,000 ft.                                   8 ft. 
                10,000 ft.                                   7 ft. 
 

                                                                                  5